Gas Fitting Types

      It is absolutely critical that only trained personnel disconnect and re-connect medical gas cylinders. Mishandling, not connecting the cylinders correctly, or cross connecting gases can lead to serious injury and even death.

  • do not attempt to modify the cylinder connections

  • always verify that the gas cylinder label matches the CGA fitting type for that particular gas

  • only trained personnel should replace cylinders

  • never remove or change the fittings on the gas cylinders

Oxygen (O2):

      NFPA 99 color: green
      connection type: CGA-540


click image to enlarge

Air:

      NFPA 99 color: yellow
      connection type: CGA-346


click image to enlarge

Nitrogen (N2):

      NFPA 99 color: black
      connection type: CGA-580


click image to enlarge

Nitrous Oxide (N2O):

      NFPA 99 color: blue
      connection type: CGA-326


click image to enlarge

Carbon Dioxide (CO2):

      NFPA 99 color: gray
      connection type: CGA-320


click image to enlarge

Medical Breathing Mixtures:

      NFPA 99 color: varies (consult your gas supplier)
      connection type: CGA-280

 


click image to enlarge

 
 

© 2006, Medical Gas Info. All Rights Reserved

bulletNote to visitors
bulletIndustry Links
bulletTrade Shows

bulletMedical Gases and their Use
bulletWAGD info
bulletDryer technologies
bulletVacuum pump technologies
bulletAir compressor technologies
bulletGas outlet styles
bulletGas fitting types
bulletNFPA Changes

bulletDefinitions
bulletUseful formulas
bulletConversion charts

bulletSource equipment sizing
bulletPipeline sizing
bulletNFPA alarm points
bulletMounting heights for products
bulletFlow Requirements

bulletAsk a question
bulletQuestions & Answers
bulletContact us
bulletPrivacy policy

bulletUsed equipment
bulletIndustry job openings